Department of Chemical Engineering I.I.T. Bombay, India Closed Loop Transfer Functions Unlike in the open loop case, the closed loop has two independent inputs, viz. the set point and the disturbance. Assuming that all other elements such as valve and sensors are lumped with the process dynamics, the block diagram can be drawn as, d disturbance + + y d y Plant controller u + -
Department of Chemical Engineering I.I.T. Bombay, India Closed loop response of first order + proportional (P) control K For g p (s)= and g c (s)=K c, the response to a unit step at the s 1 set point is given by, KK c 1 KK 1 s 1 c y ( s ) KK s 1 KK c 1 s 1 c s 1 1 KK c The system responds like a first order process with a smaller time constant and a gain close to unity. The steady state error between the set point (unit step) and the process output y(t) is called the offset. Most processes under proportional control exhibit offset.
Department of Chemical Engineering I.I.T. Bombay, India Closed loop response of first order + (PI) control t 1 dy and u ( t ) K ( y y ) ( y y ) dt y Ku c d d dt I 0 t dy 1 Therefore, y KK ( y y ) ( y y ) dt c d d dt I 0 2 d y dy KK c ( 1 KK ) y y 1 c d 2 dt dt I Therefore the closed loop transfer function is second order with lead, KK ( s 1 ) c I y ( s ) y ( s ) d 2 s ( 1 KK ) s KK 1 I I c c This could yield oscillatory response with possible overshoot. For a unit step change, it will reach set-point and exhibit zero offset. Integral action therefore increases the effective order of the system but gives zero offset.
Department of Chemical Engineering I.I.T. Bombay, India Closed loop response of first order + (PI) control Integral action causes off-set to be zero High proportional gain causes oscillatory response High integral action leads to sluggish response
Department of Chemical Engineering I.I.T. Bombay, India Closed loop response of first order + (PD) control d dy and u ( t ) K y Ku c D dt dt Therefore the closed loop transfer function is first order with lead term, KK ( s 1 ) c D y ( s ) y ( s ) d ( KK ) s 1 KK c D c The overall order is therefore actually reduced. Transient response will be that of a lead lag system. It will exhibit steady state offset. Likewise for PID control, the closed loop transfer will have 2 poles and 2 zeros and due to integral mode, it will not exhibit offset.
Department of Chemical Engineering I.I.T. Bombay, India Closed loop response of first order + (PID) control Derivative action leads to stability due the lead term in the transfer function.
Department of Chemical Engineering I.I.T. Bombay, India Derivative mode illustration : on-off control of a heater.
Department of Chemical Engineering I.I.T. Bombay, India Controller types for feedback control Proportional + Integral Controller t 1 c ( t ) p ( t ) p K ( t ) ( t ) dt s c I 0 where c is the controller output, (t) is the error and p s is the output at zero error. c ( s ) 1 g ( s ) K 1 c c ( s ) s I The term I is called the integral time, reset time and the reciprocal is called the reset time.
Department of Chemical Engineering I.I.T. Bombay, India Controller types for feedback control Proportional + Integral + Derivative Controller t 1 d ( t ) c ( t ) p ( t ) p K ( t ) ( t ) dt s c D dt I 0 where c is the controller output, (t) is the error and p s is the output at zero error. c ( s ) 1 g ( s ) K 1 s c c D ( s ) s I The term D is called the derivative time constant.
Department of Chemical Engineering I.I.T. Bombay, India Integral action and offset removal Consider that at steady state, the steam flow rate is 100 kg/hr and the temperature is 200 o C. Suppose that a setpoint change to 205 o C is introduced. Let us now consider how a P and PI controller would behave at steady state in closed loop. du ( t ) d ( t ) and therefore c The equation is K u ( t ) K ( t ) c dt dt du ( t ) d ( t ) At steady state, rate of change is zero and therefore 0 dt dt This could happen only if is a zero or a non-zero constant. If is a zero, the deviation in steam flowrate u will be zero and also error between setpoint and CV is zero. This is not possible physically as you cannot get temperature to rise without supplying additional steam. Therefore, = 0
Department of Chemical Engineering I.I.T. Bombay, India Integral action and offset removal t K c For PI control, the equation is u ( t ) K ( t ) ( t ) dt c I 0 du ( t ) d ( t ) 1 and therefore K ( t ) c dt dt I du ( t ) d ( t ) At steady state, rate of change is zero and therefore 0 dt dt This means that the error must go to zero at steady state and the extra control effort comes from the integral term. This ensures that a nonzero deviation in the control effort is available through integral action.
Department of Chemical Engineering I.I.T. Bombay, India Anti-reset wind up schemes
Department of Chemical Engineering I.I.T. Bombay, India Anticipatory action of the derivative mode Period Sign of Type of More or Corrective sign of Effect of error current less action de/dt derivative action necessary action (0,t 1 ) positive heating more decrease negative decrease heat heat (t 1 ,t 2 ) negative cooling less increase negative increase cooling cooling (t 2 ,t 3 ) negative cooling more decrease positive decrease cooling cooling